P3 INC-1005 · Medium · reported by Mira Kälin (Monitoring)
Bern: network alarm, no user impact so far
-
Mira Kälin (Monitoring) Report 13:47:01
At 13:47 the alerts for Bern fired: links went down and the traffic moved to the backup paths. Traffic still flows, nobody called yet. Can the NOC take a look?
-
NOC-POC System 14:24:00
SLA breached: nobody solved this incident in time. The fault was repaired.
Post-mortem
- Root cause
- jdoe's configuration change on core-brn-2 administratively shut its uplink.
- Fault
- Bad config change (wrong uplink shut)
- Right answer
- D: Roll back the last configuration change on core-brn-2
- Solved by
- Nobody: SLA breached
At 13:47:00 jdoe changed the configuration of core-brn-2 and shut Hu1/0/51 (DOWNLINK dc-spine-1 Eth1/54) instead of an unused port. Traffic moved to the redundant uplink; the admin-down interface is the clue.
Causal chain
- jdoe's configuration change on core-brn-2 administratively shut its uplink.
- core-brn-2--dc-spine-1 stopped carrying traffic; the devices at both ends logged the loss (if they could reach srv-mon).
- Redundancy carried the traffic after convergence: nothing else became unreachable.
- What was noticed: monitoring alarms only; users kept working on the redundant path.
Why the other options were wrong
- Replace the fan tray of core-brn-2 before it overheats Wrong: it assumed the fans of core-brn-2 had failed. Right place, wrong fault: core-brn-2 had no such problem. The cause: jdoe's configuration change on core-brn-2 administratively shut its uplink.
- Replace the fan tray of core-brn-1 before it overheats Wrong: it assumed the fans of core-brn-1 had failed. core-brn-1 was healthy: no alarm, its sensors and power supplies were normal. The cause: jdoe's configuration change on core-brn-2 administratively shut its uplink.
- Roll back the last configuration change on core-brn-1 Wrong: it assumed a configuration change on core-brn-1 broke it. core-brn-1 was healthy: no alarm, its sensors and power supplies were normal. The cause: jdoe's configuration change on core-brn-2 administratively shut its uplink.
Timeline
- 13:47:01 INC-1005 opened: Bern: network alarm, no user impact so far (Mira Kälin (Monitoring))
- 14:24:00 SLA breached; fault repaired
Inbox
7- P2 INC-1007 7:22 Bern: network almost unusable Open
- P4 INC-1006 13:22 Bern: hardware alarm, no user impact Open
- P3 INC-1005 Bern: network alarm, no user impact so far SLA breached
- P2 INC-1004 Many failed logins on the network devices SLA breached
- P2 INC-1003 Bern: Intranet unavailable, devices not answering SLA breached
- P2 INC-1002 Bern: Intranet unavailable, devices not answering Resolved
- P3 INC-1001 Metrics and logs missing from some routers Resolved